Configuring the MVI69-103M Module

MVI69-103M ♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 23 of 131

November 3, 2008

8 When you have finished editing, save the file and close Notepad.

Important: Changes to the configuration file will not take effect until you download the file to the
module, and then reboot the module.

2.2 [Backplane

Configuration]

2.2.1 Module

Name

0 to 80 characters

This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.

2.2.2 Read Register Start

Range 0 to 3999

This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0
to 3999.

2.2.3 Read Register Count

Range 0 to 3999

This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999.

2.2.4 Write Register Start

0 to 3999

This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module.

2.2.5 Write Register Count

Range 0 to 3999

This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999

2.2.6 Failure Flag Count

0 through 65535

This parameter specifies the number of successive transfer errors that must
occur before the communication ports are shut down. If the parameter is set to 0,
the communication ports will continue to operate under all conditions. If the value
is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.