Using the RSLogix 5000 v16 Add-On Instruction

MVI56-DFCM ♦ ControlLogix Platform

User Manual

DF1 Half/Full Duplex Master/Slave Serial Communication Module

Page 26 of 106

ProSoft Technology, Inc.

September 24, 2014

2 Select the 1756-M

ODULE

(G

ENERIC

1756

M

ODULE

)

from the list and click OK.

This action opens the N

EW

M

ODULE

dialog box.

3 In the N

EW

M

ODULE

dialog box, enter the following values.

Parameter

Value

N

AME

DFCM

D

ESCRIPTION

Enter a description for the module. Example: DF1 Half/Full
Duplex Master/Slave Serial Communication Module

C

OMM

F

ORMAT

Select D

ATA

-INT

S

LOT

Enter the slot number in the rack where the MVI56-DFCM
module is located

I

NPUT

A

SSEMBLY

I

NSTANCE

1

I

NPUT

S

IZE

250

O

UTPUT

A

SSEMBLY

I

NSTANCE

2

O

UTPUT

S

IZE

248

C

ONFIGURATION

A

SSEMBLY

I

NSTANCE

4

C

ONFIGURATION

S

IZE

0

Important: You must select the C

OMM

F

ORMAT

as D

ATA

-

INT in the dialog box, otherwise the

module will not communicate over the backplane with the ControlLogix processor.

4 Click OK

to continue.

5 Edit the Module Properties.