3 slc-500 command set functions – ProSoft Technology MVI56-DFCM User Manual

Page 93

Advertising
background image

MVI56-DFCM ♦ ControlLogix Platform

Reference

DF1 Half/Full Duplex Master/Slave Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 93 of 106

September 24, 2014

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

151

0x0F

0x01

Word Range Read

(ASCII Address)

X

X

152

0x0F

0x26

Read-Modify-Write
(ASCII Address)

X

X

5.3.3 SLC-500 Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

501

0x0F

0xA1

Protected Typed
Logical Read With

Two Address Fields

X

X

502

0x0F

0XA2

Protected Typed
Logical Read With

Three Address Fields

X

X

X

509

0x0F

0XA9

Protected Typed
Logical Write With

Two Address Fields

X

X

510

0x0F

0XAA

Protected Typed
Logical Write With

Three Address Fields

X

X

X

511

0x0F

0XAB

Protected Typed
Logical Write With
Mask (Three Address

Fields)

X

X

Each command list record has the same general format. The first part of the
record contains the information relating to the communication module and the
second part contains information required to interface to the DF1 slave device.

The PLC-5 and SLC-500 command set require the use of files. These files are
emulated in the module. The module defines these files each as containing 200-
word registers that overlay the internal database. The following table shows the
relationship of the files to the user data area of the internal database.

File

Database Register

N7:0

0

N8:0

200

N9:0

400

N10:0

600

N11:0

800

N12:0

1000

N13:0

1200

N14:0

1400

N15:0

1600

N16:0

1800

N17:0

2000

Advertising