Ladder Logic

MVI56-DFCM ♦ ControlLogix Platform

User Manual

DF1 Half/Full Duplex Master/Slave Serial Communication Module

Page 46 of 106

ProSoft Technology, Inc.

September 24, 2014

This action opens the Select Module dialog box:

2 Select the 1756-M

ODULE

(G

ENERIC

1756

M

ODULE

) from the list and click OK.

This action opens the New Module dialog box.

3 Enter the Name, Description and Slot options for your application. You must

select the Comm Format as D

ATA

-

INT in the dialog box, otherwise the

module will not communicate. Click OK to continue.

Parameter

Value

Name

Enter a module identification string. Example: DFCM_2

Description

Enter a description for the module. Example: DF1

H

ALF

/F

ULL

D

UPLEX

M

ASTER

/S

LAVE

S

ERIAL

C

OMMUNICATION

M

ODULE

Comm Format

Select D

ATA

-INT.

Slot

Enter the slot number in the rack where the MVI56-DFCM
module is located.

Input Assembly Instance

1

Input Size

250

Output Assembly Instance

2

Output Size

248

Configuration Assembly Instance

4

Configuration Size

0