ProSoft Technology MVI56-DFCM User Manual

Page 72

Advertising
background image

Reference

MVI56-DFCM ♦ ControlLogix Platform

User Manual

DF1 Half/Full Duplex Master/Slave Serial Communication Module

Page 72 of 106

ProSoft Technology, Inc.

September 24, 2014

After the module has received the Module Configuration Block from the
processor, the module will begin communicating with other nodes on the
network, depending on the configuration.

Main Logic Loop

Upon completing the power up configuration process, the module enters an
infinite loop that performs the following functions:

Call I/O Handler

Call CFG/DEBUG Port

Driver

Call Network Master &

Slave Drivers

Call I/O Handler

Transfers data between the module and processor

(user, status, etc.)

Call Serial Port Driver

Rx and Tx buffer routines are interrupt driven. Call to

serial port routines check to see if there is any data

in the buffer, and depending on the value, will either

service the buffer or wait for more characters.

Call Network Master & Slave Drivers

Generate messages and

respond to messages received.

From Power Up Logic

ControlLogix Processor Not in Run

Whenever the module detects that the processor has gone out of the Run mode
(that is, Fault or PGM), the DF1 ports can be shut down as prescribed in the user
configuration. When the processor is returned to a running state, the module will
resume communications on the network.

Backplane Data Transfer

The MVI56-DFCM module communicates directly over the ControlLogix
backplane. Data is paged between the module and the ControlLogix processor
across the backplane using the module's input and output images. The update
frequency of the images is determined by the scheduled scan rate defined by the
user for the module and the communication load on the module. Typical updates
are in the range of 2 to 10 milliseconds.