MVI56-DFCM ♦ ControlLogix Platform

Diagnostics and Troubleshooting

DF1 Half/Full Duplex Master/Slave Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 51 of 106

September 24, 2014

The bits in each configuration word are shown below. The module configuration
error word has the following definition:

Bit

Description

Value

0

Read block start value is greater that the database size.

0x0001

1

Read block start value is less than zero.

0x0002

2

Read block count value is less than zero.

0x0004

3

Read block count + start is greater than the database size.

0x0008

4

Write block start value is greater that the database size.

0x0010

5

Write block start value is less than zero.

0x0020

6

Write block count value is less than zero.

0x0040

7

Write block count + start is greater than the database size.

0x0080

8

0x0100

9

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

The port configuration error words have the following definitions:

Bit

Description

Value

0

Type code is not valid. Enter a value from 0 (Master) to 1 (slave).

0x0001

1

Protocol parameter is not valid.

0x0002

2

Termination type parameter is not valid.

0x0004

3

Baud rate parameter is not valid.

0x0008

4

Parity parameter is not valid.

0x0010

5

Data bits parameter is not valid.

0x0020

6

Stop bits parameter is not valid.

0x0040

7

Command count parameter is not valid.

0x0080

8

Retry count parameter is not valid.

0x0100

9

Invalid Override File Map Count

0x0200

10

Spare

0x0400

11

Spare

0x0800

12

Spare

0x1000

13

Spare

0x2000

14

Spare

0x4000

15

Spare

0x8000