2.5.1 PROFIBUS Master Port Specifications

Type

Specifications

General Parameters

Internal Database

Up to 4000 registers (words) available.

Communication parameters

Baud Rate: 9.6 kbps to 12 Mbps

PROFIBUS Master

Command List

Read Diag
Global Cmd
Read Cntrs
Reset Cntrs

Status Data

Error codes available on an individual command
basis. In addition, a slave status list is maintained
per active PROFIBUS Master port.

PROFIBUS Master

Node address

0 to 125 (software selectable)

Status Data

Error codes, counters and port status available per
configured slave on the network.

2.5.2 PROFIBUS Master Port Access to Database

Virtual

Database

Command

List

Other

Driver

PROFIBUS

Driver

Slave

Device

Databases

Other

Protocol

PROFIBUS

Master

PROFIBUS

Slaves

Request

Response

Read

Read for

Write Command

Write for Read

Command

Write

Read

The Master driver uses the database in two ways:

1 A read command issued to a slave device by the master driver will return the

slave data into the internal database.

2 A write command issued to a slave device by the master driver uses the data

in the internal database to write to the slave device.