Reference

PDPM ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DP Master

Page 64 of 70

ProSoft Technology, Inc.

June 24, 2013

Wiring diagram for a PROFIBUS DP cable

Grounding and Shielding for Systems with Equipotential Bonding
Each cable shield should be galvanically grounded with the earth using FE/PE
grounding clamps immediately after the cable has been connected to the cabinet.

This example indicates the shielding connection from the PROFIBUS cable to the
FE/PE rail.

Note: An equalization current can flow across a shield connected at both ends because of
fluctuations in ground potential. To prevent this, it is imperative that there is potential equalization

between all the attached installation components and devices.

This example indicates the system components and devices in a system with
equipotential bonding.