Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.

Byte

Bit Position

Designation

7

6

5

4

3

2

1

0

0

Lock
Reg

Unio
Req

Sync
Req

Free
Req

WD
on

Res

Res

Res

Station status

1

WD_Fact_1

2

WD_Fact_2

3

MinTSDR

4

Ident_Number_High

5

Ident_Number_Low

6

Group_Ident

7

Spec_User_Prm_Byte

8 to
243

User_Prm_Data

Byte 7

Spec_User_Prm_Byte

Bit

Name

Significance

Default State

0

Dis_Startbit

The start bit monitoring in the
receiver is switched off with
this bit

Dis_Startbit = 1,
That is, start bit monitoring is
switched off.

1

Dis_Stopbit

Stop bit monitoring in the
receiver is switched off with
this bit

Dis_Stopbit = 0

That is, stop bit monitoring is not
switched off.

2

WD_Base

This bit specifies the time
base used to clock the
watchdog.
WD_Base = 0: time base 10
ms
WD_Base = 1: time base 1 ms

WD_Base = 0
That is, the time base is 10 ms.

3 to 4

Res

To be parameterized with 0

0

5

Publisher_Enable

DXB-publisher-functionality of
the SPC3 is activated with this
bit

Publisher_Enable = 0, DXB-
request-telegrams are ignored;
Publisher_Enable = 1, DXB-
request-telegramme are processed

6 to 7

Res

To be parameterized with 0

0