PDPM Protocol Configuration

PDPM ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DP Master

Page 46 of 70

ProSoft Technology, Inc.

June 24, 2013

4.2.3 254 - Read Cntrs

If the Data Length parameter is set to zero, the command will reset the counters
for all slaves. If the Data Length is specified, it represents the number of slaves
to read the static counter data. The Node Address specifies the first slave node
to consider in the request. The counter data returned is placed at the Database
Address in the command.

4.2.4 Command 70 Control Byte

The Freeze and Sync commands are used for synchronization purposes. The
Freeze command causes a slave to freeze its inputs and the Sync command
causes a slave to hold the outputs.

Bit

Definition

0

Reserved

1

Clear output data

2

Unfreeze input data

3

Freeze input data

4

Neutralize the sync command

5

Freeze output data until sync command is neutralized

6

Reserved

7

Reserved

Bit 2 or 4

Bit 3 or 5

Definition

0

0

No function

0

1

Function will be activated (that is, Freeze input data)

1

0

Function will be inactivated (that is, Unfreeze input data)

1

1

Function will be inactivated (that is, Unfreeze input data)