IntelliKnight 5820XL Installation Manual

5-10

151209

5.8

Addressing SD Devices

This section explains how to address SD detectors and modules.

5.8.1

SD505-APS, SD505-AHS, & SD505-AIS

The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and
SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer
Code is required to perform this task.

To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in

Figure 5-7. (You can use the same base for each detector).

Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing

2. Enter the Installer code, then press

.

3. Select

for Point Functions.

4. Select

for Set SLC Dev Addr.

5. Select “Yes” by pressing the

up arrow, then press

. (The panel will go into

trouble at this point. You can use the

key to stop the PZT. The trouble will

clear automatically when the panel re initializes when you finish programming).

6. When the wait message clears, the following options display:

for Read Address. Use to read (or check) a single detector’s address.

for Write Address. Use to program a single detector’s address.

for Seq. Programming. Use to program more than one detector in sequential

order.

7. If you are changing addresses, write the programmed address on the back of the

device.

8. To exit press

left arrow until fully exited.