IntelliKnight 5820XL Installation Manual

4-38

151209

4.12.4 Installing 4-Wire Smoke Detectors

Any compatible U.L. listed four-wire smoke detector can be used with the control
panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure
4-35 illustrate how to connect a UL listed four-wire detector to the control panel.

4.12.4.1 Installing a Class B 4-Wire Smoke Detectors

Figure 4-36 illustrates how to install a 4-wire Class B smoke detector.

Conventions used for wiring 4-wire Class B loops:

1. Up to three Class B 4-wire smoke detector loops can be connected to the control

panel at once.

2. Each Class B loop input is paired with a unique power source as shown in Figure

4-36.

3. Each loop gets smoke power from the even numbered Flexput circuit and the con-

tact input is connected to the odd numbered Flexput circuit.

Figure 4-36 Class B 4-Wire Smoke Detector Connections

Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is

used to refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in
programming it would be referred to as point 5.

Air Products

PAM-2

Model 160150

Supervision

Module

UL Listed

EOL Resistor

Model 7628

ESL 449CT

Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.

Supervised
Power Limited