Control Panel Installation

151209

4-33

4.12.1.2 Class A Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix at
the back of this manual.

To install a Class A notification appliance circuit:

1. Wire the Class A notification appliances as shown in Figure 4-31.

2. Configure the circuit for Class A in programming (see Section 7.6).

Figure 4-31 Class A Notification Appliance Circuit Configuration

Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is

used to refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in
programming it would be referred to as point 5.

Caution

For proper system supervision do not use looped wire under terminals marked O and X of the Flexput
connectors. Break wire runs to provide supervision of connections.

Supervised
Power Limited

Regulated 24 VDC Full Wave Rectified

27.4 VDC, 3A per Circuit, 6A max Combined