Control Panel Installation

151209

4-31

4.12 Flexputs

I/O Circuits

The six Flexput™ circuits are an innovative and versatile feature of the control panel.
They can be used as: Class A or B notification circuits, Class A or B initiation circuits
(either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door
holder).

The polarity of the Flexput terminals differs depending on whether the circuit is
programmed as an input or and output circuit. If the circuit is programmed as an input
circuit (for a detector or normally open contact) the X terminal is negative and O
terminal is positive. If the circuit is programmed as an output circuit (Aux power or
NAC) then the X terminal is positive and the O terminal is negative.

This section of the manual explains how to install conventional notification appliances
and initiating devices to be used with the system.

4.12.1 Conventional Notification Appliance

This sub-section of the manual explains how to install conventional notification
appliances for Class A (Style Z) and Class B (Style Y) configurations.

4.12.1.1 Class B Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix A at
the back of this manual.

To install a circuit:

1. Wire Class B Notification appliances as shown in Figure 4-30.