151209

1-1

Section 1
Introduction

The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire
control system that meets the requirements of UL 864.

1.1

Overview of Basic System

The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit
boards mounted to an aluminum housing.

1.1.1

Hardware Features

The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s)
support the SK series addressable detectors and modules or SD protocol
detectors and modules.

Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors
and 396 modules per 5820XL panel when using SK series devices. Alternatively,
each SLC supports up to 127 SD devices for a total of 508 devices per 5820XL
panel.

6.0A of output power is available through 6 sets of terminals for notification and
auxiliary applications. Each circuit is power limited per UL 864 and can source up
to 3.0A (total output power for all 6 circuits must not exceed 6.0A).

Built-in dual phone line, digital alarm communicator/transmitter (DACT).

Reports events to central station by point or by zone.

UL Listed for pre-action and deluge releasing systems.

Dedicated Form C trouble relay and two general purpose Form C programmable
relays.

Basic system operation can be performed using a key or a user code.

Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).

Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight
devices on one control panel. See sections 4.8 and 4.9 for additional information
on these models.

Printing of detector status, event history, and real time event log available through
the Model 5824 Serial/Parallel Printer Interface Module (sold separately).

Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.

Add six Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight
5895XLs per system). See note below.

Add four notification/auxiliary power circuits with each 5496 Intelligent Power
Module. See note below.

Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any