Honeywell INTELLIKNIGHT 5820XL User Manual

Page 36

Advertising
background image

IntelliKnight 5820XL Installation Manual

3-12

151209

1. Total does not include isolator devices or accessory bases.

2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or

240 VAC.

3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is

removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.

4. Use next size battery with capacity greater than required.

5865-4 LED Annunciator
(with reset and silence switches)

(8 max.)

Standby: 35 mA

mA

Alarm: 145 mA

mA

5865-3 LED Annunciator

Standby: 35 mA

mA

Alarm: 145 mA

mA

5880 LED I/O Module

Standby: 35 mA

mA

Alarm: 200 mA

mA

5883 Relay Interface

(32 max.)

Standby: 0 mA

mA

Alarm: 220 mA

(22 mA per relay)

mA

A

Total System Current

Auxiliary Devices

3

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

B

Auxiliary Devices Current

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours:

H

G

Multiply lines E and F.

Total standby AH

AH

H

Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)

H

I

Multiply lines E and H.

Total alarm AH

AH

J

Add lines G and I.

4

Total ampere hours

required

AH

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current