IntelliKnight 5820XL Installation Manual

3-2

151209

3.3

Electrical Specification

Table 3-1 list the terminal block on the 5820XL as well as a description of each
individual terminal and their respective electrical rating.

Table 3-1: Terminal Descriptions and Electrical Specifications

Terminal # and Label

Description

Rating

Earth Ground

Faults

Voltage

Current

1

L

AC input (hot)

120 VAC, 60 Hz 2.5 A

N/A

2

Earth ground

N/A

N/A

N/A

3

N

AC input (neutral)

120 VAC 60 Hz

2.5 A

N/A

4

X

*I/O 6

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

5

O

100 mA for initiation
circuits

6

X

*I/O 5

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

7

O

100 mA for initiation
circuits

8

X

*I/O 4

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

9

O

100 mA for initiation
circuits

10

X

*I/O 3

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

11

O

100 mA for initiation
circuits

12

X

*I/O 2

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

13

O

100 mA for initiation
circuits

14

X

*I/O 1

Flexput™ Circuits

24 VDC

3.0A notification and
auxiliary power circuits

0

15

O

100 mA for initiation
circuits

16

B

SBUS
OUT

SBUS communication

5 VDC

100 mA

0

17

A

18

+

SBUS power

24 VDC

1.0 A

19

-

20

B

SBUS IN

Used for Class A installations

0

21

A

22

+

23

-

24

N.C.

RELAY 2

General Purpose Relay 2

24 VDC

2.5 A, resistive

N/A

25

C

26

N.O.

*

Regulated for NAC circuits, special application when used for releasing.