Testing and Troubleshooting

151209

10-3

condition is transmitted.

2) Notify facility personnel of a test so that alarm sounding devices are ignored during
the test period.

3) When necessary, activation of Notification Appliances can be prevented by the
DISABLE function

Testing:

1) Activate a input via an alarm initiating device and check that the correct outputs
activate (Notification Appliances sound/flash, relays activate, alarm LED lights).
Reset system. Repeat for each alarm initiating device.

2) Momentarily open the following circuits one at a time and check for a trouble
signal:

Notification Appliance (bell) Circuits.

Initiating devices

3) If new batteries were installed, wait 48 hours before completing this step.
Remove AC power, activate initiating device and check that:

The ALARM indicator lights.

All active Notification Appliances sound.

Measure battery voltage while the Notification Appliances are sounding. Replace any
battery with terminal voltage less than 85% of rating. Reapply AC power and RESET
system.

10.2.2 Event History

The event history can be useful for tracking or recalling a trouble condition.