7-40

151209

60 Hz. selection

To change the AC line frequency, continue programming from step 9 above:

10. Select 50, 60 or Neither, by pressing the

or

arrow, then press

.

7.7.5

Miscellaneous Options 2

Through this programming option you can turn the strobe synchronization during
silence feature On or Off, and select the control panel to report events by zone or by
point.

To edit miscellaneous options 2:

1. Enter the installer code.

2. Press

or

to display the main menu.

3. Select

for Program Menu.

4. Select

for System Options.

5. Select

for Miscellaneous Options 2.

7.7.5.1 Synchronize Strobes Active During Silence

When “SYNC Strbs w/ Sil:” is Selected as Y (Yes) then strobes will continue to flash
when the system is silenced and will stop flashing when the system is reset.

Note: The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.

6. Press the

or

arrow to toggle this selection between Y (Yes) or N (No).

7. Press

or

to make your selection and move to the next programming option.

Note: See Section 7.4.1.4 for more information about Synchronization protocol choices.

7.7.5.2 Auto Display Oldest Event

When this feature is programmed Y (Yes) then the oldest un-acknowledge event will
automatically display on the control panel and remote annunciators after there has
been no activity on any system touch-pad for two minutes.

8. Press the

or

arrow to toggle this selection between Y (Yes) or N (No).

9. Press

or

to make your selection and move to the next programming option.

7.7.5.3 Report by Zone or by Point

When the “Report by” option is set to Zone, then the control panel will report events
by zone. If Point is selected then the control panel will report events by point.