Section 7
Programming

This section of the manual describes how to manually program the control panel from
the built-in annunciator. Each subsection discusses these menu options in detail. All
options described in this section can be performed using the 5660 Silent Knight
Software Suite (SKSS).

7.1

UL 864 Programming Requirements

Important!

Before any customized programming is done, JumpStart should be run first.
After JumpStart is run, thoroughly test the system. The reason the system
should be tested after JumpStart is because Jumpstart automatically programs
the system, searching for and configuring all SLC and SBUS devices it finds.
JumpStart allows you to confirm the integrity of the installation prior to
performing any custom programming. After determining that the hardware is
properly installed, custom programming can be performed. Refer to Section 6.

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND

OTHER INVOLVED PARTIES: This product incorporates field programmable software.

In order for the product to comply with the requirements in the Standard for Control Units

and Accessories for Fire Alarm Systems, UL 864, certain programming features or

options must be limited to specific values or not used at all as indicated below.

Programming Option

Menu Item

Permitted in

UL 864 (Y/N)

Possible

Settings

Settings

Permitted in UL

864

Misc Options 1

Low AC Report

Delay

Yes

0–30 hours

1–3