Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 14

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

12

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

4.5.1.2 Installation

procedure:

input voltage 120Vac (optional, 5-6kVA only), output voltage 120/208/220/230/240Vac.

If a battery extension pack is to be installed, please proceed with section 4.5.5.

If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.5.6.

The numbers between (brackets) refer to figure 19 and 20 in section 5.1.

1. Mount the levellers: position A to fix the UPS to the

floor, position B to lift the castors from the floor.

Please refer to figure 6, step 1.

2. Loosen the screws and remove the conduit boxes

(17, 2x) and the cover plate (11).

3. Make sure that all circuit breakers (7-8-9) are in ‘off’

position (down). Please refer to fig. 6, step 3.

4. Input/output

connection:

Lead the input/output cables through the cable inlet. If

the cables come from below (recommended for 8kVA

and 10kVA models), you can rotate the cable inlet 90

degrees. Connect the input wires to the input

terminals (11b). Connect the output wires to the

output terminals (11a). Please refer to section 4.5.2.2

(input) and 4.5.3 (output) for detailed information.

5. Re-install the cover plate (11) and the conduit boxes

(17, 2x).

6. An emergency shutdown switch can be connected to

connector J3 on the RS232/Contact Interface Card,

between pins 3 and 4. See section 6.2 for more

information.

7. For advanced communication possibilities, the

RS232/contact interface port (12a) can be connected

to a computer system. See section 6.1 for more

information.

8. The middle ‘option slot’ (13) allows easy installation of

plug-in cards: SNMP Card or Relay Card. See

sections 6.3 and 6.4 for more information.

9. The right ‘option slot’ (14) allows easy installation of

the RPA-card (Redundant Parallel Architecture). If the

card is already mounted, and if the unit is intended to

be used stand-alone, a bus terminator (delivered with

the unit) has to be placed in one of the two bus

connectors on the card. If the unit will be part of a

parallel system, see sections 4.5.6 and 7.3 for more

information.

10. Connect the utility power to the UPS.

11. If hardware modifications were necessary in step 4

because the output voltage is different from the

default (208Vac), software modifications should be

performed as well. Proceed with 4.5.4.

12. For a quick start proceed with section 5.2 ‘Start-up’.

Figure 7. LP 5/6-11U:

Installation procedure 120V input

2

see 6.3-4

see 4.5.6 / 7.3

stand-alone
and RPA card
available

BATTERY

DISCONNECTED


EMERGENCY

SHUTDOWN

4

5

6 7

8 9