Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 46

Advertising
background image

Digital Energy

LP Series

g

LP 5/6/8/10-11U installation drawings

Model Heat

dissipation

Linear load 240 Volt

Dimensions Air

flow

100%

load

Rel.

humidity

non-cond.

Altitude

(max 4000m)

Input wiring

Output wiring

100% load

50% load

h

w

d

Weight

Amb.

temp.

utility

volt.

120V

utility volt.

208V

utility volt.

240V

output

volt. 120V

output

volt. 208V

output

volt. 240V

LP-U W

Btu/hr

W

Btu/hr

Inch

Inch

Inch

Lbs

m3/hr

°F

m

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

5-11

571 1950 389 1329 26.8 12.3 28.7 295 660 14-104 <95

N.A.

10/6

10/6

8/10

10/6

10/6

6-11

661 2254 381 1300 26.8 12.3 28.7 295 660 14-104 <95

N.A.

8/10

10/6

8/10

10/6

10/6

8-11

948 3234 551 1882 26.8 12.3 28.7 386 660 14-104 <95

N.A.

6/14

8/10

6/14

8/10

8/10

10-11

1090 3719 556 1896 26.8 12.3 28.7 410 660 14-104 <95

N.A.

4/22

6/14

4/22

8/10

8/10

5-11/120

V 641 2187 425 1451 39.2 12.3 28.7 386 660 14-104 <95

6/14

N.A.

N.A.

8/10

10/6

10/6

6-11/120

V 744 2539 601 2051 39.2 12.3 28.7 386 660 14-104 <95

<1000, derating

12.5% per 1000

4/22 N.A. N.A. 8/10 10/6 10/6

Model

Minimum free space required

(Inches)

front side rear

Distance between mounting

holes (Inches)

Input overcurrent protection
(AMPS)

Output overcurrent protection (AMPS)

LP-U

x

y

z 120V 208V 240V 120V

(1 X)

120V
(2X)

208V 240V

5-11

4 2 8 7.24

22.76

7.48

35 30 40 20 25 20

5-11

/120V 4 2 8

7.24

22.76

7.48

60 40

20

25 20

6-11

4 2 8 7.24

22.76

7.48

40 35 50 25 30 25

6-11

/120V 4 2 8

7.24

22.76

7.48

70 50

25

30 25

8-11

4 2 8 7.24

22.76

7.48

60 45 70 35 40 35

10-11

4 2 8 7.24

22.76

7.48

70 60 80 40 50 40

Advertising