LX: OPM_LPU_11U_5K0_10K_1US_V030

40

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

UPS

Type

:

5-11U 6-11U 8-11U 10-11U

Output power (kVA/kW)

: 5/4

6/4.8

8/6.4

10/8

AC input voltage

: 120/208/240 Vac (120V only with step-up transformer for LP 5/6-11U)

Input frequency

: 60/50 Hz

AC output voltage

: 120/208/220/230/240V

Output frequency

: 60 or 50 Hz, std. 60 Hz; selectable on front

System efficiency (full load)

: 87%

Line input breaker (C-type)

: 32A

32A

50A

63A

Bypass input breaker (C-type)

: 32A

32A

50A

63A

Battery safety fuse (F4A)

: 30A

30A

30A

30A

Battery safety fuse (F4B)

: 30A (spare) 30A (spare) 30A

30A

Internal safety fuse (F5A)

: -

-

30A

30A

Internal safety fuse (F5B)

: 30A

30A

30A

30A

Input/output connectors

: terminals at rear of unit

INPUT

AC input voltage range (208V-240V)

at 100% load

: 162 - 285 V

at 50% load

: 146 - 285 V

at 20% load

: 133 - 285 V

AC input voltage range (120V, L5/6-11U)

at 100% load

: 81 - 141 V

at 50% load

: 72 - 141 V

at 20% load

: 66 - 141 V

Input frequency range

: 40-70 Hz

Input current wave form

: sinusoidal

Input power factor

:

0.99

Max. input current at 100% load

120V : 43.3A

50.8A

n.a.

n.a.

208V

:

25.0A

30.0A

40.5

50.3

240V

:

21.4A

25.1 34.8 42.0

Inrush current

: none

Rectified DC voltage out

: 380 V

BATTERY CHARGER

Characteristic

: U/I-characteristic, constant current charging until boost/float voltage, then

constant voltage charging and boost charge mode for fast recharging of

batteries

DC input voltage range

: 350-450 V

DC output voltage at 20 °C

: float: 273 V boost: 295 V

Output current limit (Adc)

: 2.0

2.0

3.0

3.0

OUTPUT CONVERTER

Output power at pf. = 0.8, VA*

: 5000

6000

8000

10000

Semiconductor :

IGBT

AC output voltage

: 120/208/240V ± 1% static resistive load

120/208/240V ± 2% measured crest load 2.5:1

120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of

rated load applied or removed

Typical overload

: 110%

20 minutes

(temp. dependent)

130%

3.5 minutes

150%

2 minutes

Output frequency

: 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility

Freq. tracking range

: ± 2/4/6% of nominal, user selectable

Output wave form

: sine wave

Max. phase difference input-output

: max 7

°

Harmonic distortion

: 2% max. with linear load

Power factor range

: Any lagging or leading power factor permitted within the specified rating to

pf. 0.5

Output derating altitude

: Till 1000m no derating

Above 1000m 12.5% per 1000m, max. 4000m

Protection

: Automatic shut down (or transfer to bypass, if bypass is available) in case of

- low/high DC voltage

-

overtemperature

- overload / short circuit

The output is protected against connection to the utility supply

* according to EN 50091-1