Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 31

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

29

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

Service information on internal timer.

Frequency tracking range: output converter frequency will follow the bypass

frequency within these limits before returning to its own internal frequency.

Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%.

See 5.3.4 Set-up Menu.

No-load shutdown: after a 10 minutes delay the UPS will shut down during

utility failure if the load is < 2%. It will restart after the utility returns or when the

unit is switched off and on again.

Default setting = 1 (active). For disabling this feature see 5.3.4.

Start of the manual Quick Battery Test.

See for more information section 5.4.2 'Quick Battery Test'

Start of the manual Deep Battery Calibration Test.

See for more information sections 5.4.3 'Deep Battery Calibration Test'

Service information on internal UPS components

Service information on internal UPS components

Service information on internal UPS components

Batt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging,

4 = maintenance charge

Duration of latest test performed, hh/mm/ss

The UPS transfers the load to bypass when the keys 'down' (2) and

'Enter/Reset' (3) on the front panel are depressed simultaneously for approx. 1

second. If the bypass supply is not within limits, the lower line will show the

text 'UNAVAILABLE'.

Service set-up information whether the bypass is enabled (default) or disabled.

If disabled: UPS will NOT go to bypass. For disabling the bypass refer to the

set-up menu (5.3.4).

Service set-up information about the total battery capacity. Information about

the actual battery charge condition. For changing the programmed battery

capacity refer to the set-up menu (5.3.4).

Service set-up information about frequency tracking speed for the inverter to

follow the bypass frequency, LOW (1Hz/sec.) is the normal value and default.

HIGH (5Hz/sec.) may be suitable if the UPS is connected to a generator with

fast frequency changes and the UPS must be synchronized to prevent alarms.

For changing the lock speed refer to the set-up menu (5.3.4).

Service set-up information about the ECO-mode. By pressing ‘Enter/Reset’

the ECO-mode can be enabled or disabled, depending on the actual status.

In this way the load will be supplied by way of the electronic bypass. If the

ECO-mode is disabled the load will be supplied by the inverter. See also

5.5.5.

Service set-up information about the autorestart function. This function can

be switched on or off by pressing ‘Enter/Reset’, depending on the actual

status. See also 4.5.6.

TSTAMP Q4
6028773 1

FREQ RANGE: 2%
NO LOAD : 1

QUICK BATTERY
TEST PRESS ENTER

CALIBRATE BAT
PRESS DOWN+ENTER

PF1 THYRISTOR 1
BATT.THYRISTOR 0

VSS THYRISTOR 0
PF1. CONVERTER 1

LAST TEST TIME
0:00:00

BAT CHARGER 2
INVERTER 1

FORCE BYPASS
press DOWN+ENTER

AUTOMATIC BYPASS
ENABLED

BATTERY 7Ah
BAT. CHARGE 86%

PLL LOCK SPEED
NORMAL

ECO DISABLED
ENTER/RESET CHNG

AUTO RESTART ON
ENTER/RESET CHNG