LX: OPM_LPU_11U_5K0_10K_1US_V030

27

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

LOADnotPROTECTED
BATTERY DEPLETED

LOADnotPROTECTED
BATTERY LOW

UPS SHUTDOWN
LEFT 2 MINUTES

BYPASS ERROR
FUSE FAILURE

After 24 hours of charging time, the battery voltage did not reach the normal

float voltage. This may be caused by faulty batteries, too many battery packs

connected or a charger fault.

The main DC-capacitor needs replacement due to aging or failure

Due to a failure the output converter's output is not available. As a result the

load may have been transferred to bypass.

The remaining runtime is zero. As a result the load may have been transferred

to bypass.

The remaining run time is less than the set time (standard 2 minutes). This text

alternates with the following screen:

The output voltage can be lost after the indicated time due to discharged

battery. Controlled shutdown of any computer equipment is absolutely

necessary at this point. (Using the RS232 or SNMP communications interface,

this procedure can be initiated automatically on unattended systems). If the

UPS operates at 100% load, the shutdown procedure should be completed

within 2 minutes after the 'battery low' alarm started. When the batteries are

fully discharged, the UPS is no longer able to power the connected equipment.

The static bypass circuit breaker (rear panel, 9) is in 'off' (down position): no

bypass voltage available. Utility voltage is available. If not manually operated,

this may have been caused by an overload situation.

The utility circuit breaker (rear panel, 8) is in the 'off' (down position): no line

voltage available, bypass voltage is available. If not manually operated, this

may have been caused by an internal system failure.

The internal battery fuse is defective; this may have been caused by an

internal system failure. This alarm also appears if no batteries are installed.

The (custom-built) battery extension set has been disconnected from the

system: its energy reserve is not available. See 4.5.2 step 12 for details.

The batteries are (almost) chemically worn out. If the batteries are aged, they

must be replaced as soon as possible to ensure full protection for your

equipment (see section 8.3).

The utility voltage or utility frequency are outside UPS input tolerance (see

chapter 10, specifications)

The utility voltage or utility frequency are outside bypass input tolerance but

inside UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass

operation is inhibited: if for whatever reason the output converter is unable to

deliver the required output, output power is lost.

BATTERY CHARGER
NO FLOAT

CAPACITOR C1
CAPACITY LOW

LOADnotPROTECTED
INVERTER OFF

INPUT ERROR
FUSE FAILURE

INTERNAL BATTERY
FUSE FAILURE

REPLACE BATTERY

INPUT out LIMITS
137V 60.0Hz

BYPASSoutLIMITS
197V 60.0Hz

EXTERNAL BATTERY
FUSE FAILURE