Digital energy, Lp series, 3 - functional explanation – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 9: 1 the principles of operation, 2 normal conditions, 3 utility failure

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

7

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

3.1

The Principles of Operation

The UPS stores electric energy in batteries. This allows the UPS to supply output power even when the

incoming utility power is cut off completely.

Energy is stored as Direct Current (DC), while input and output energy must be Alternating Current (AC).

Therefore the UPS contains an input converter (AC to DC) and an output converter (DC to AC). (fig.2)

3.2 Normal

Conditions

Under normal conditions, energy from the utility is channeled through the input converter, which supplies the

output converter and the battery charger. The batteries are kept in a fully charged state, and the output

converter synthesizes a completely new AC output sine wave to supply the load (electrical equipment).

3.3 Utility

Failure

In the event of a utility power failure (i.e. absent or outside tolerance) the system uses the energy reserve

stored in the battery to continue to produce AC power, ensuring unbroken output (fig. 3). No interruption or

alteration will ever be noticed in the output power.

In the event of an extended utility failure, the output converter will stop when the battery has been discharged.

At this point, the UPS is no longer able to power the connected equipment.

When the utility is re-established within tolerance, the output converter will be supplied again by the input

converter and the batteries will be recharged, making them ready to support future power failures.

Figure 2. Block diagram of the LP 11U UPS, utility present

Figure 3. Block diagram of the LP 11U UPS, utility failure

3 - Functional Explanation

INPUT:
MAINS POWER WITH DISTURBANCES

BYPASS

FILTER

P.F. = 1

CONVERTER/

RECTIFIER/

BATTERY

CHARGER

BACKFEED

PROT.

OPTIONAL

BATTERY

EXTENSION

BATTERY

MICROPROCESSOR CONTROL

SYSTEM

ON/OFF

OUTPUT

CONVERTER

MANUAL BYPASS

SWITCH

UTILITY INPUT

OUTPUT:
PERFECT UPS POWER

RFI

FILTER

OPTION

SLOTS FOR:

RPA CARD

SNMP CARD

RELAY CARD

STANDARD

INSTALLED:

RS232/

CONTACT

INTERFACE

FRONT

PANEL

TO LOAD

RFI

FILTER

STATIC

BYPASS

OUTPUT

TRANSFORMER

NO INPUT:
UTILITY FAILURE

BYPASS

FILTER

P.F. = 1

CONVERTER/

RECTIFIER/

BATTERY

CHARGER

OPTIONAL

BATTERY

EXTENSION

BATTERY

MICROPROCESSOR CONTROL

SYSTEM

ON/OFF

OUTPUT

CONVERTER

MANUAL BYPASS

SWITCH

OUTPUT:
PERFECT UPS POWER

RFI

FILTER

OPTION

SLOTS FOR:

RPA CARD

SNMP CARD

RELAY CARD

STANDARD

INSTALLED:

RS232/

CONTACT

INTERFACE

FRONT

PANEL

TO LOAD

RFI

FILTER

STATIC

BYPASS

OUTPUT

TRANSFORMER

BACKFEED

PROT.

Advertising