LX: OPM_LPU_11U_5K0_10K_1US_V030

31

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

Controls functioning of the automatic bypass switch. Range:

ENABLED/DISABLED. If the UPS is used as a frequency converter you may

change the setting to ‘DISABLED’. Bypass operation will then be inhibited and

all alarms related to ‘bypass out of limits’ are suppressed.

The system can prompt for service to a user defined schedule.

Range: 8/12/16/20/24/28 months or DISABLED. To reset the timer: first select

“DISABLED” and subsequently set a new alarm interval.

5.4 Test

Screens

These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS

monitoring software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.

Upper lines:

second line:


GENERAL SYSTEM

GENERAL SYSTEM

GENERAL SYSTEM

GENERAL SYSTEM

TEST START

TEST START

TEST START

TEST START

the test will start soon

QUICK BATTERY

QUICK BATTERY

QUICK BATTERY

QUICK BATTERY

TEST ACTIVATED

TEST ACTIVATED

TEST ACTIVATED

TEST ACTIVATED

the test is running

CALIBRATE BAT

CALIBRATE BAT

CALIBRATE BAT

CALIBRATE BAT

TEST SUCCESFUL

TEST SUCCESFUL

TEST SUCCESFUL

TEST SUCCESFUL

the test has been completed succesfully

BYPASS

BYPASS

BYPASS

BYPASS

TEST FAILED

TEST FAILED

TEST FAILED

TEST FAILED

the test has not been completed succesfully

5.4.1 Battery Test, general

Automatic test: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the

batteries and the wiring are able to support power failures. The tests do not cause any interruption in the

functioning of the unit.

Manual test: A manual battery test can be activated

- either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of

your interface package), or

- via the front panel: see below

5.4.2 Quick Battery Test

From the standard menu first enter the service menu (press the 'down' and 'Enter/Reset' keys simultaneously,

then press the 'down' key until the following screen appears:

The ‘Enter/Reset’ key confirms the selection, and the screen shows:

The test status (indicated by the second line) can be:
TEST ACTIVATED

TEST ACTIVATED

TEST ACTIVATED

TEST ACTIVATED =

testing

TEST SUCCESSFUL

TEST SUCCESSFUL

TEST SUCCESSFUL

TEST SUCCESSFUL

=

battery has been tested with positive result

TEST FAILED

TEST FAILED

TEST FAILED

TEST FAILED

=

the batteries should be replaced

NOT AVAILABLE

NOT AVAILABLE

NOT AVAILABLE

NOT AVAILABLE

=

battery capacity too low to start the test

If the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will be generated.

The batteries must be replaced as soon as possible (see section 8.3).

NOTE: If the manual test is started immediately after installation or after a power failure, the UPS may generate

a false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during

the power failure.

QUICK BATTERY
TEST PRESS ENTER

QUICK BATTERY
TEST START

AUTOMATIC BYPASS
ENABLED

SERVICE WARNING
DISABLED