Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 28

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

26

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

5.3.2 Status and Alarm Menu

The UPS alerts the user with a standard alarm screen that the operating mode has changed and/or that an

alarm situation occurs:

The actual operating mode, the possible modes are mentioned below. The

lower line -if displayed- shows that an alarm occurred. More information can

be retrieved with the 'up' key. If no further information is available, the second

line is blank.

Possible operating modes:
ON LINE

The normal operating mode. For more information see section 3.2.

ON BYPASS

Overload or failure situation. For more information see section 3.5.

ON BATTERY

For a detailed description of this mode see section 3.3.

OUTPUT OFF

No power is delivered to the load. This can be the result of a command via the
RS232 Port, or because no electric energy is available (utility failure, depleted

batteries).

ON MANUAL BYPASS

Service mode. For more information see section 3.6.

on ECO-mode

ECO-Mode. See section 5.5.5

Depressing the 'up’ key from the standard alarm screen shows, in priority order, which alarms are active,. Scroll

through the screens with the 'up' and 'down' keys. Alarm message texts can succeed each other. The following

messages are possible:

The output capacitor C2 is defective. Contact your dealer.

The load exceeds the rated output power of the UPS, and the output voltage

can no longer be guaranteed. This text alternates with the following screen:

showing the actual load as % of the nominal UPS rating. These messages are

displayed if the load is > 100%.

If the load exceeds 150% the UPS will immediately switch to bypass,

assuming that the conditions for a transfer to bypass are fulfilled. If an

overload condition between 100-150% persists, the UPS can eventually also

switch to bypass operation due to temperature protection. If a transfer to

bypass is inhibited (due to voltage or frequency errors of the utility supply) the

UPS may automatically switch off within a few seconds (load dependent).

Output power is lost at that moment. To avoid these problems, be absolutely

certain that the power demands of the protected equipment are within the

limits of the UPS.

The temperature of the heatsinks or output transformer is too high. As a result

the output voltage may be transferred to bypass.

The operating temperature can rise to intolerable levels as a result of:

extreme environmental temperature

lack of proper ventilation

an overload situation

fan

failure

If the UPS operates in 'on line' mode, it will switch to bypass until the

temperature is normal again. If however the UPS operates 'on battery', a

shutdown will occur and output power is lost.

The internal DC voltage is too high, internal failure

The output voltage of the battery charger is too high, internal failure

The battery temperature is too high due to a battery failure or a too high

ambient temperature

ON LINE

ALARM PRESS UP

LOADnotPROTECTED
CAP. C2 DEFECT

UPS OVERLOADED
REDUCE LOAD

UPS OVERLOADED
LOAD 143%

LOADnotPROTECTED
TEMP TOO HIGH

LOADnotPROTECTED
VOLTAGE TOO HIGH

BATTERY CHARGER
VOLTAGE TOO HIGH

BATTERY CHARGER
TEMP TOO HIGH

Advertising