The UPS is equipped with 3 ‘option slots’ (rear panel, 12-14). In the most left slot (12) an RS232/contact

interface card is factory installed. See 5.1. In the middle slot (13) additional Relay or SNMP plug-in Cards can be

installed. The most right slot (14) allows easy installation of an RPA plug–in Card (Redundant Parallel

Operation).

6.1 RS232 / contact interface

The RS232/Contact interface (9-pole, sub D, rear panel, 12a) enables advanced communication between the

UPS and e.g. a personal computer. An interface kit (cable and software) is delivered with the UPS. The

software supports most common operating systems incl. Novell, UNIX, VMS, Windows 3 - 95/98/2000 - NT,

IBM OS/2, LINUX, has a modular and layered architecture and works for all degrees of network complexity:

stand-alone, multi-vendor networks and large managed networks.

During a power failure the UPS software takes a number of actions: processes are stopped, open files are

closed and unattended systems will be shut down in a controlled way. When the utility power returns, the

systems will automatically start up and will be up and running as soon as possible.

For specific information on GE Digital Energy™ connectivity products please contact your dealer or internet:

www.gedigitalenergy.com.


Pin #

Function

1

Battery

low

2

Serial data out

3

Serial data in / UPS shutdown

4

Not

used

5

Common

6

Bypass

active

7

Plug&Play / RTS

8

Utility

failure

9

General

alarm

contact interface: Max 48V / 30mA

6.2 Emergency

shutdown

The emergency shutdown connector is located on the RS232/contact interface card (12). Be sure that the UPS

is switched off, and remove the card from the unit*. Remove the wire from connector J3 (pin 3 and 4). Install the

wiring of a normally closed contact to connector J3 (pin 3 and 4). Re-install the RS232 interface card. If during

normal operation of the UPS the contact is opened, the UPS will shut down. To restart the unit, restore the

connection and turn the UPS off and on again.

* If the card is removed during normal operation the UPS will shut down.

6.3 Relay Card (optional)

The relay plug-in card can be installed in the middle option slot (rear panel, 13). The card is provided with four

potential free contacts representing: battery low, bypass active, utility failure and general alarm. For more

information please refer to the user manual that comes with the interface card.

6.4 SNMP Interface (optional)

This SNMP plug-in card can be installed in the middle option slot (rear panel, 13). The card makes the UPS

‘SNMP manageable’: it allows the data interface to be connected directly to an Ethernet network (thin coax,

twisted pair, AUI). For more information please refer to the user manual that comes with the interface card.

When this option is installed the RS232 communication link is no longer available.

Fig. 22: RS232 / contact interface