Digital energy, Lp series, 9 - troubleshooting – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 41

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

39

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or load) to

determine whether the problem is caused by the unit itself or by its environment. Subsequently check whether

the breakers/switches on the rear panel (fig. 19, 7-8-9) are in ‘on’ position. Always check these external factors

before concluding that your UPS is faulty.

The front screen will indicate the problem and solution (if the problem is due to environmental circumstances). If

the solution is not shown on the screen, please contact your dealer.

During the self-test, performed immediately after start-up, the UPS may detect a system failure. In this case a

message is displayed for 30 seconds before the self-test is repeated. If the faulty situation persists, please

contact your dealer.

(One of) the following messages can be displayed:

One or more voltages of the internal power supply is (are) outside

tolerance. Please contact your dealer.

An external AC voltage (not the UPSs output voltage) was detected on the

output terminals. Please contact your dealer.

The internal battery fuse is defective. Please contact your dealer.


The battery extension circuit breaker is in 'the off' position. Please switch it

to 'the on' position.

Malfunction of the battery charger. Please contact your dealer.

Malfunction of the input circuit: voltage delivered is too high. Please contact

your dealer.

The temperature of (one of) the components is (still) too high. See section

5.3.2.

The battery voltage is too low to allow start-up. Wait for a few hours, leave

the UPS switched on.*

Malfunction of input circuit: voltage delivered is too low. The batteries may

be faulty or depleted. Wait for a few hours, leave the UPS switched on.*

Hardware output voltage detection 'Q4' is active. Please contact your

dealer.

* If absence of input power (utility failure, maintenance work) is expected to last longer than a few hours, switch

off the UPS to save battery power. If the UPS input power is absent for several days and the UPS remains on

under no-load conditions, the batteries can be discharged very deeply, resulting in a short battery life time.

SELFTEST FAILURE
PCB POWER SUPPLY

SELFTEST FAILURE
AC ON INPUT

SELFTEST FAILURE

INT.BATTERY FUSE

SELFTEST FAILURE
EXT.BATTERY FUSE

SELFTEST FAILURE
BATTERY CHARGER

SELFTEST FAILURE
Uic TOO HIGH

SELFTEST FAILURE
TEMP TOO HIGH

SELFTEST FAILURE
Uba TOO LOW

SELFTEST FAILURE
Uic TOO LOW

SELFTEST FAILURE

Q4 NOT OK

9 - Troubleshooting