Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 20

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

18

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

4.5.5

Installation of GE Digital Energy LP-U battery extension pack(s)

The numbers between (brackets) refer to figures 19-21 in section 5.1.

Battery extension pack(s) are shipped with all materials necessary to connect them to the UPS. The pack(s)

can be connected to the DC connector (15) at the rear panel of the UPS. Be sure to switch off the UPS before

proceeding: be sure that the UPS can be switched off without causing damage to the load, and turn all circuit

breakers (7-8-9) into ‘off’ position (down).

1. Open the DC fuse holders at the rear of the battery

pack (16) and make sure that the fuses have been

removed.

1a. Open the DC fuse holders at the rear of the UPS (16)

and make sure that the fuses have been removed.

2. UPS rear panel: loosen the screws, and remove the

cover plate (11) and conduit box (17).

CAUTION!

The battery voltage is 240Vdc

and is NOT isolated from the utility.

3. Break out the indicated part of the conduit box, fix the

gland of the DC cable in this opening.

4. Connect the DC connector of the battery pack (15a)

to the DC socket of the UPS (15). Be sure that the

colours match. You will hear a click when the cable is

properly installed.

5. Re-install the cover plate and conduit box.

6. In case of 14Ah battery packs: using the DC

connector of the battery pack (15) you can install a

second, third, etc. pack. 7Ah battery packs cannot be

connected in parallel.

NOTE: A maximum of two Digital Energy™ 14Ah

battery cabinets can be connected without additional

fusing. Every two additional Digital Energy™ 14Ah

battery cabinets must be connected over a 60Amp

fuse, rated for 300Vdc.

NOTE: Third party battery cabinets must be

connected over a 60Amp fuse, rated for 300Vdc,

using the Digital Energy™ external battery cable

(order separately).

7. Insert the 2 (7Ah) or 4 (14Ah) DC fuses of the (each)

battery pack, insert the DC fuses of the UPS and

close the fuse holder(s) of battery pack and UPS (16).

8. In order to calculate the available back-up time

related to the actual load, information on the capacity

of the battery set is stored in the UPS. As the total

battery capacity changes when battery extension

packs are installed, the battery capacity must be re-

programmed. See 5.3.4.

In case of a custom-built battery extension set you may

want to install a ‘battery disconnected’ alarm device.

9. Be sure that the UPS is switched off, and

disassemble the RS232/Contact Interface Card (12)

from the unit. If the card is disassembled during

normal operation the UPS will shut down!

Remove the wire from connector J3 (pin 1 and 2).

Install the wiring of a normally closed contact (e.g. an

auxiliary contact of a circuit breaker) to pin 1 and 2.

Re-install the interface card. If the contact is opened,

the UPS will generate an ‘EXTERNAL BATTERY

FUSE FAILURE’. See 5.3.2 for more information.

Proceed with 4.5.1 or 5.2.

Figure 16. LP 5/6/8/10-11U:

Installation of battery pack

1

2

3

4

5

1a

Advertising