Digital energy, Lp series – GE Industrial Solutions LP11U 5-10kVA User Manual

Page 43

Advertising
background image

LX: OPM_LPU_11U_5K0_10K_1US_V030

41

GE DE LP 11U UPS: Installation / User Manual 3.0 (US)

Digital Energy

LP Series

g

UPS

Type

:

5-11U 6-11U 8-11U 10-11U

AUTOMATIC BYPASS SWITCH

The automatic switch provides transfer of the load to the utility voltage without any interruption of the supply. The transfer is

initiated by a signal from the output converter protection circuit in case of an overload or high temperature.

When the conditions return to normal the load is automatically transferred back to the output converter. The automatic

bypass switch can be disabled by the end-user.

Bypass voltage limits

: -15%, +10% of nominal

Transfer transients

: typically 2% mean deviation over one half cycle.

Frequency tracking range

: ± 2/4/6% of nominal (user selectable)

Slew rate

: max. 1Hz/sec or 5Hz/sec (user selectable)

BATTERY

Battery type

: Sealed and maintenance free

Nominal voltage (V) / capacity (Ah)

: 12/7

12/7

12/12

12/12

Number of batteries

: 20

20

20

20

Capacity of standard battery set

: 7Ah

7Ah

12Ah

12Ah

Battery recharge time

: 1.5 - 3 hours for 80% capacity

Battery service life

: up to 6 years (depending on operating conditions)

Battery discharging

: self discharge current

0.35 mA

discharge end voltage of the battery depending on the actual load

10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA

When the UPS is in sleeping mode the inverter will be switched off, battery

charger and rectifier are in operation

Runtime in minutes

VA / Watts

1000 / 800

: 6060

120

120

2000 / 1600

: 4040

60

60

3000 / 2400

: 1818

40

40

5000 / 4000

: 1010

22

22

6000 / 4800

: - 8

17

17

8000 / 6400

: - -

11

11

10000 / 8000

: - -

-

8

BATTERY EXTENSION PACKS

Sheet steel cubicle

: VSDA1

Dimensions (hxwxd, mm)

: 537x313x590

Dimensions (hxwxd, inch)

: 21.1x12.3x23.2

Battery

: 240Vdc/7Ah or 240Vdc/14Ah

Weight with battery (Kg)

: 73 or 123

Weight with battery (Lbs)

: 161 or 271

Battery pack A (voltage V / capacity Ah)

: 240/7

240/7

240/7

240/7

Total capacity (Ah)

: 14

14

19

19

Typical runtime, 100% / 50% load, min.

: 25/60

21/50

22/50

16/39

Number of packs required

: 1

1

1

1

Battery pack B (voltage V / capacity Ah)

: 240/14

240/14

240/14

240/14

Total capacity (Ah)

: 21

21

26

26

Typical runtime, 100% / 50% load, min.

: 45/90

35/75

33/70

25/57

Number of packs required

: 1

1

1

1

For more info see section 7.1

STEP-UP TRANSFORMER CABINET MOUNTED UNDERNEATH VSD2 (FOR LP 5/6-11U ONLY)

Sheet steel cubicle

: VSDT2 + VSD2

Dimensions (hxwxd, mm)

: 995x313x730

Dimensions (hxwxd, inch)

: 39.2x12.3x28.7

Weight (Kg)

: 175 Kg

Weight (Lbs)

: 386 Lbs