1 tiiildd…<cr, Tiiildd…<cr – ICP DAS USA I-7540D User Manual

Page 59

Advertising
background image

4.1

tIIILDD…<CR>

Description: Send or receive a standard CAN data frame.

¾

Syntax: tIIILDD…<CR>

t

Represent a standard (2.0A) data frame.

III

11 bits Identifier (000~7FF)

L

Data length (0~8)

DD…

Input data frame value according to the data length

(00~FF)

¾

Response:

Valid command: No response

Invalid command: ?<Error Code><CR>

¾

Note:

It is necessary to enable the “Error Response” function in the i-7540D
Utility, in order to receive Syntax and/or communication error information
at the host PC.

¾

Example:

Command: t03F6112233445566<CR>
Send a CAN message with a standard data frame. ID=03F, DLC=6,

data1=11, data2=22, data3=33, data4=44, data5=55 and data6=66


Note:

This command can only be accepted by 7540D’s port

10003

i-7540D CAN-Ethernet Gateway User’s Manual (Version 1.4, April/2008)

59

Advertising