4.8 99#P01

Description: Read the RS-232 configuration

¾

Syntax: 99#P01

99#P01

Command character

¾

Response:

Valid Command: 061BBDSP

Invalid command: ERROR

061

Delimiter for valid command

BB

RS-232 Baud rate

D Data

bit

0 = 7 bits data formation

1 = 8 bits data formation

S Stop

bit

0

=

1

stop

bit

1

=

2

stop

bits

P Parity

bits

0

=

None

1

=

Even

2

=

Odd

RS-232 Baud rate list

BB Description

00

110 bps baud rate of RS-232

01

150 bps baud rate of RS-232

02

300 bps baud rate of RS-232

03

600 bps baud rate of RS-232

04

1200 bps baud rate of RS-232

05

2400 bps baud rate of RS-232

06

4800 bps baud rate of RS-232

07

9600 bps baud rate of RS-232

08

19200 bps baud rate of RS-232

09

38400 bps baud rate of RS-232

0A

57600 bps baud rate of RS-232

0B

115200 bps baud rate of RS-232