Ground converter shelves, Figure 5 converter shelf mounting, Figure 6 converter shelf ground – GE Industrial Solutions CPS2400U User Manual
Page 11
Advertising
CPS2400U Upstream System – 19” Product Manual
CPS2400U
850028186 r04 December 2013
11
Figure 5 Converter Shelf Mounting
Ground Converter Shelves
Fan shelves will be grounded when connecting input power.
Step
Action
1.
Run and connect the framework ground lead
to safety grounding point (frame ground, or main ground bar) per local practice.
6 AWG minimum
Apply NO-OX ID to all bare metal connections if required by local practice.
Torque to 35 in-lb (4 Nm).
Figure 6 Converter Shelf Ground
Lugs landings - 1/4” studs on 5/8” centers.
Lugs for 6AWG conductor - T&B 6STR30W , Burndy YAV6C-L2TC14-FX or available equivalent:
2.
Repeat from for remaining Converter Shelves.
Ground Lead