CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

11

Figure 5 Converter Shelf Mounting

Ground Converter Shelves

Fan shelves will be grounded when connecting input power.

Step

Action

1.

Run and connect the framework ground lead

to safety grounding point (frame ground, or main ground bar) per local practice.
6 AWG minimum
Apply NO-OX ID to all bare metal connections if required by local practice.
Torque to 35 in-lb (4 Nm).

Figure 6 Converter Shelf Ground

Lugs landings - 1/4” studs on 5/8” centers.
Lugs for 6AWG conductor - T&B 6STR30W , Burndy YAV6C-L2TC14-FX or available equivalent:

2.

Repeat from for remaining Converter Shelves.

Ground Lead