CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

25

Troubleshooting

Only Remote Power System specific alarms are included in this section. See Galaxy Pulsar Edge Product Manual for details of other controller alarms.
Many alarms are best processed at the converter shelf alarm card and converter card level.
LAN port or Craft port access provides additional information – see Galaxy Pulsar Edge Product Manual for details

System

Table 1 System Troubleshooting

Controller

Alarm Card

Converter Card

Possible Problem

Possible Solution

Alarm Display

Back-

light

Relay

State

Alarm

LED

State

Relay

State

OK

LED

State

Alarm

LED

State

Normal

Green

Green

none

Various

Yellow

or Red

Green

Green

Latched Controller Alarm

or Alarm for Removed

Equipment

Execute Controller commands “Clear Events” and

“Uninstall Equipment”.

Controller – Control/Operations

Web Pages – Maintenance tab.

Circuit Fail

Yellow

Min

Yellow

Min

Green

Flashing

Yellow

Short + to -

Make sure each converter has an independent

isolated send and return path.

Circuit Fail

Yellow

Min

Yellow

Min

Flashing

Red

Flashing

Red

Short to Ground

Make sure each converter has an independent

isolated send and return path.

Communication

Fail

Yellow

Min

Yellow

Min

Green

Off

1 Card Removed

Check to see that all cards are seated.

Replace non-functioning cards.

Communication

Fail

Red

Maj

2 Cards Removed

Check to see that all cards are seated.

Replace non-functioning cards.

Communication

Fail

Red

Maj

Flashing

Red

Green

Off

Communication Cable

Removed

Check communication path from alarm cards to

Controller.

If controller is not present, set alarm card rotary

switch to Shelf ID 0,0 for contact closures only

communication.

Communication

Fail

Red

Maj

Green

Flashing

Red

Alarm Card Removed

Replace Alarm card.

None

Green

Green

Yellow

Standby

Remove unit from standby if desired using

Controller or web page interface

Circuit Fail

Yellow

Min

Yellow

Min

Green

Flashing

Yellow

Open Fuse

Replace Converter.

Note: Replacing a Converter storing will interrupt

service to the other line served by the Converter.