Alarm card alarm states, Table 3 alarm card state leds and relays – GE Industrial Solutions CPS2400U User Manual

Page 28

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

28

Table 3 Alarm Card State LEDs and Relays

Alarm States

LEDs

6

Relays

7

,

6

Converter

State

-48 V Feed

State

Fan Shelf

State

OK LED

ALM LED

PMN

PMJ

OK

OK

OK

Green

Minor

OK or Minor

OK or Minor

Amber

PMN

OK or Minor

Minor

OK or Minor

Amber

PMN

OK or Minor

OK or Minor

Minor

Amber

PMN

Major

any

any

Red

PMJ

any

Major

any

Red

PMJ

any

any

Major

Red

PMJ

any

Unpowered

8

any

PMN PMJ

Alarm Card Alarm States

Alarm states are ranked from low severity to high severity.

Alarm State

Severity

Major or PMJ ....................... Highest

Minor or PMN ...................... Medium

None or OK .............. Lowest (no alarm)

Alarm states are aggregated and combined into successively larger representations:
Converter circuit states are aggregated into a Converter Card state.
Converter Card states and -48V Input Feed states are aggregated and combined into a Converter Shelf state.
Converter Shelf states and Fan Shelf states are aggregated and combined into a Converter system state.

System Alarm State - the highest alarm state within the system, including Converter Shelves and Fan Shelves.
Shelf Alarm State - the highest alarm state within the shelf, including Converter Cards and -48V Input Feeds,

Fan Shelf state (if wired), and Alarm Card I

2

C to RS-485 communication processor.

OK

No alarms are active – all OK

PMN

Minor alarms only are active

PMJ

Major – at least one major alarm is active

Fan Shelf Alarm State – the alarm state of the connected Fan Shelves.

Each Fan Shelf has a single alarm that is active when one or more fans have failed or when Fan Shelf DC

voltage is low.
OK

No Fan Shelves have alarms are active – all OK

Minor One Fan Shelf has alarm active

Major Two Fans Shelves have alarms active

Converter Card Alarm State - the highest alarm state of all Converter Cards within the shelf

OK

No Converter alarms are active – all OK

Minor at least one Minor Converter alarms only is active

Major at least one Major Converter alarm is active

-48V Input Feed Alarm State – the alarm state of the four -48V shelf feeds: - Table 2.

OK

None

Minor One input feed Low

Major Multiple input feeds Low

6

Empty cells indicate: OK for inputs, OFF for LEDs, and non-alarm for relays.

7

Alarm relays are energized (powered) in the non-alarm state.

8

The Alarm card is redundantly powered by all four -48V input feeds.