Inspect the network, Check and mark wiring compliance, Verify ul installation compliance – GE Industrial Solutions CPS2400U User Manual

Page 16

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

16

Inspect the Network

Check and Mark Wiring Compliance

The system is classified as an A2 circuit tested according to GR-1089-CORE Issue 3. As such, each location in the

network where the output is available to be touched must be protected and marked as an A2 voltage.

Step

Action

1.

Is accessibility to the circuit throughout the network consistent with A2 requirements?

2.

Is the 5-pin protector marked as a special circuit?

3.

Does the 5-pin protector protect each pair to a level corresponding to a CommScope 3C*EW Gas tube

primary protector?

This protector has a voltage breakdown range of 265-465 Volts and an impulse spark over range of

<265-700 Volts. Protectors with a lower voltage breakdown rating will be problematic.

Verify UL Installation Compliance

This verification is required at the time of installation to meet UL60950-21.

Perform this verification before power is distributed in the network.


Normally the final step is performed by closing the circuit using a 5-pin protector after DC power is applied to the

system.

Step

Action

1.

Recognize that the Remote Feed Telecommunication Voltage limited (RFT-V) circuit is voltage limited to

+190V and -190V from ground.

2.

Is the total capacitance to ground on each line of the circuit less than 10μF?

The QS982 introduces 4.4μF. The remote electronics and line must introduce less than 5.6 μF of

capacitance. .

3.

Is the total capacitance line to line of the circuit less than 40μF?

The QS982 introduces 2.2μF. The remote electronics and line must introduce less than 37.2 μF of

capacitance from tip to ring.

4.

Is the remote equipment also a RFT-V voltage limited circuit?

Both ends of the circuit must be designed to the same standard. This must be verified before the

equipment is connected together.

5.

Is the voltage rating of the Network Wiring sufficient to support 190V to ground?

6.

Is the wire between the converters and primary protectors minimum 26AWG 200V rated?

7.

Is the chassis of the system bonded to ground?

Verify by both observation and measurement before powering the system. Measurement from the

exterior of the Converter Shelf to the cabinet ground bus should indicate continuity as determined via a

meter providing an audible beep or the standard method of continuity verification used in the network.

Many network providers use a maximum value of 10 ohms.

Advertising