Converter leds, Figure 24 converter leds and test points, Table 4 converter leds – GE Industrial Solutions CPS2400U User Manual

Page 29

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

29

Converter LEDs

Figure 24 Converter LEDs and Test Points

Note: Test points work best if each voltage is measured with respect to ground.

Table 4 Converter LEDs

Action Required

OK LED

Fault LED

Conditions

Notes

None

Green

Off

All OK

Verify circuit

configuration

Off

Yellow

Standby

Standby can be set using the Controller

display or remotely using a web

browser.

Check seating on

Alarm card and

converter card

Green

Blink Red On ½ second,

Off ¼ second

Loss of comm.

Check 5 pin

protectors and faults

to ground

Red Blink

Red Blink

Ground fault

Check output lines

for shorts to each

other

Green

Yellow Blink

Overcurrent or under

voltage

Replace unit

Red Blink

Off

OV or internal failure

Solve Thermal

problem

Off

Red Blink

Thermal Alarm

Latch off after 3 retry cycles

Check source

voltage

Off

Off

card not powered or

input fuse failure

Observe Lamp Test

Bi-Color: 4.5 seconds

on, 4.5 seconds on and

1 second off

Bi-Color: 4.5 seconds

on, 4.5 seconds on and

1 second off

Lamps test requested

from controller

Display Examples

LED Display

9

Conditions

Action Required

All OK

None

Circuit Placed in Standby

None depending on desired state of the circuit

Standby state can be set using the controller or

web browser.

9

Examples in the table are shown for conditions on the B circuit of the QS982A card. The same Conditions and Actions

apply for the A circuit when A circuit LEDs are illuminated.

Advertising