Alarm Card Office Alarms
Each Shelf provides alarm contact closures for Power Major and Power Minor. Wire these relays into the alarm network
if desired.
Systems equipped with a controller provide all alarms via the controller alarm connector and require no office alarm
wiring to alarm cards.
Inter-Shelf Signal Cables are only required between Fan Shelves and the adjacent Converter Shelf in systems without a
Controller.
Step
Action
1.
Install Alarm Card Cables
Attach the office alarm leads to the office alarm screw terminals of alarm card TB1 per site engineering
instructions.
Figure 35 Alarm Card Pin Out
Figure 36 Alarm Card Cables
2.
Reinstall Alarm card and close distribution door.
Repeat for each shelf.
To Office Alarm network