Converter shelf alarm card state table, Figure 34 office alarm pin outs - alarm cards, Table 11 converter shelf alarm card states – GE Industrial Solutions CPS2400U User Manual

Page 44

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

44

Appendix C: Operation without a Controller -

Alarm Wiring

Each converter shelf provides alarm contact closures for Power Major and Power Minor independently of a controller.

Wire these relays into the alarm network in deployments where a controller is not utilized. When a controller is installed

then an alarm cable can be attached to the controller – see the Connect Office Alarms section.

Step

Action

1.

Attach the required alarm leads to the office alarm screw terminals (TB1 on the alarm card) as

designated.

Figure 34 Office Alarm Pin Outs - Alarm Cards

2.

Reinstall Alarm card and close distribution door.

Converter Shelf Alarm Card State Table

This section shows Alarm and LED response for the Alarm Card LEDs and Relays:
The Converter Shelf contains a pair of A bus feeds and a pair of B bus feeds. The use of dual A and B feeds is to not

exceed the 48 AMPS L2 input current per feed. The A bus feeds are designated A

1-6

and A

9-12

, and power shelf slots 1-6

(left side) and 7-12 (right side) respectively. The B bus feeds are also designated in an identical fashion. The alarm card

monitors the -48v on each of these four feeds, and asserts alarms and indicators - Table 11.

Table 11 Converter Shelf Alarm Card States

-48 V Input Bus

Vin LEDs

Status LEDs

Alarm Relays

17

A

1-6

B

1-6

A

7-12

B

7-12

A LED

B LED

OK LED

ALM LED

PMN

PMJ

1

OK

OK

OK

OK

GRN

GRN

GRN

OFF

E

E

2

LOW

OK

OK

OK

RED

GRN

OFF

YEL

D

E

3

OK

LOW

OK

OK

GRN

RED

OFF

YEL

D

E

4

OK

OK

LOW

OK

RED

GRN

OFF

YEL

D

E

5

OK

OK

OK

LOW

GRN

RED

OFF

YEL

D

E

6

LOW

LOW

OK

OK

RED

RED

OFF

RED

E

D

7

LOW

OK

LOW

OK

RED

GRN

OFF

RED

E

D

8

LOW

OK

OK

LOW

RED

RED

OFF

RED

E

D

9

OK

LOW

LOW

OK

RED

RED

OFF

RED

E

D

10

OK

LOW

OK

LOW

GRN

RED

OFF

RED

E

D

11

OK

OK

LOW

LOW

RED

RED

OFF

RED

E

D

12

LOW

LOW

LOW

OK

RED

RED

OFF

RED

E

D

13

LOW

LOW

OK

LOW

RED

RED

OFF

RED

E

D

14

LOW

OK

LOW

LOW

RED

RED

OFF

RED

E

D

15

OK

LOW

LOW

LOW

RED

RED

OFF

RED

E

D

16

LOW

LOW

LOW

LOW

OFF

OFF

OFF

OFF

D

D

17

E – Energized relay in non-alarm state; D – De-energized relay in alarm state