35

Specifications

Table 8 Specifications

Electrical and Thermal

Parameter

Symbol

Min

Typical

Max

Unit

Input Voltage

Operating Continuous

Non-operating, No Damage

V

I

-40

0

-52.8

-60

-40

Vdc

Transient (@ duration =)

5 seconds

V

tr

-65

V

10 ms (rise and fall rate of 10V/ms

V

tr

-75

10 µs

V

tr

-100

1 µs

V

t

-200

Input Current per half shelf

11

at 97.7W on all circuits

V

IN

= 54.4V

I

IN

26.0

Adc

V

IN

= 52.1V

I

IN

27.2

Adc

V

IN

= 42.6V

I

IN

33.2

Adc

V

IN

= 40.0V

I

IN

35.4

Adc

-48V Input Short Circuit Current Limit

12

10,000

A

Power per Converter Card

at -42.6 Vdc input

Input Power

Pin

240

13

W

Power Dissipation

Pdiss

21

40

13

W

Output Power

Pout

200

W

Output

Output Voltage (line to line)

VO

378

380

382

Vdc

Output Power (per circuit)

PO

95.0

97.7

100

W

Output Current

IOUT

251

257

262

mA

Isolation Input to Output

1500

Vdc

Temperature Ambient

Operating at airflow

14

at 150 lfm airflow

T

A

-40

50

°C

at 175 lfm airflow

T

A

-40

65

°C

at higher (TBD) airflow

T

A

-40

75

°C

Cold Start Temperature

T

A

-40

°C

Storage Temperature

T

stg

-55

85

°C

Grounding / Bonding Network: Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated

Ground Plane (Mesh-Bonding Network or Common Bonding Network).

Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;

2. can be connected to shielded intra-building cabling grounded at both ends.

Physical

Parameter

Symbol

Min

Typical

Max

Unit

Horizontal Clearance behind Shelves and Baffles

3

Inch

Component

Height

Width

Depth

Weight

Converter Shelf

3.3 in (84mm)

17.2 in (437mm) 11.9 in (303mm) 30 lb (13.6kg)

Fan Shelf

1.73 in (44mm)

17.2 in (437mm) 11.9 in (303mm)

20 lb (9.0kg)

1U Baffle

1.73 in (44mm)

17.2 in (437mm) 11.9 in (303mm)

5 lb (2.2kg)

11

Each shelf has 4 feeds: redundant A and B feeds for each side of the shelf (half shelf). Each feed must be sized to fully

power the half shelf in the event of failure of the other redundant feed.

12

-48V feeds must be wired to limit short circuit current - Table 9.

13

These are maximum situations with each circuit loaded to 100W. No actual or engineered application would load

every circuit to this level. In the absence of detailed information about the network we would recommend using the

typical dissipation value of 21 W per card for most applications and 30W per card for highly loaded networks.

14

Airflow across the entire cross section of the warmest converter shelf.