Standards compliance, Installation area, Installation environment – GE Industrial Solutions CPS2400U User Manual

Page 37: Installation category

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

37

Standards Compliance

• The equipment meets the applicable requirements of these North American product standards: UL60950-21,

UL60950-1, Telcordia GR-3108-CORE, GR-1089-CORE, GR-487-CORE (converter shelf), and GR-063-CORE.

• Baffle Required at top of each Converter Shelf Stack in CO and customer premise locations for UL compliance

(Baffles not Required in outside plant cabinets, CEVs, or huts).

• For multi-shelf systems (up to 3), this equipment has been evaluated for continuous use in ambient

temperature from -40°C to 65°C

16

.

• The main output voltage (+/-190V) meets UL60950-21RFT-V requirements.

DO NOT CONNECT TO RFT-C CIRCUITS.

Installation Area

Install only in restricted access areas (dedicated equipment rooms, equipment closets, or the like) in accordance with

articles 110-16, 110-17, and 110-18 of the U.S. National Electric Code (NEC), ANSI/NFPA No. 70, and pursuant to

applicable local codes.

Installation Environment

This equipment is to be used in controlled environments (an area where the humidity is maintained at levels that cannot

cause condensation on the equipment, the contaminating dust is controlled, and the steady-state ambient temperature

is within the range specified).

Installation Category

• Output circuits are suitable for connection to telephone lines that are equipped with primary lightning

protectors consistent with UL 497.

• Each copper pair must be provided with protection external to this equipment to a level equivalent to a

CommScope 3C*EW Gas tube primary protector [For example: 3C3EW provides the part in a red color]. This

protector has a voltage breakdown range of 265-465 Volts and an impulse spark over range of <265-700 Volts.

Protectors are provided by the telco customer.

• The 5-Pin protector must be marked as a “special circuit” consistent with the marking protocol in the users

network.

• Network equipment and components along the powering circuit shall have suitable insulation resistance at

200 Vdc from each conductor to ground and a total insulation resistance suitable for 400 Vdc from line to line.

16

-40°C to 55°C for 3 converter shelves and 2 Fan Trays when equipped with QS982A Converters.