CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

26

Table 1 System Troubleshooting

Controller

Alarm Card

Converter Card

Possible Problem

Possible Solution

Alarm Display

Back-

light

Relay

State

Alarm

LED

State

Relay

State

OK

LED

State

Alarm

LED

State

Circuit Fail

Yellow

Min

Yellow

Min

Flashing

Yellow

Under Voltage

Replace Converter.

Note: Replacing a Converter storing will interrupt

service to the other line served by the Converter.

Fan Fail

Yellow

Min

Yellow

Min

Green

Off

1 Fan Tray Failed

Replace fan shelf or tray.

Fan Fail

Yellow

Min

Yellow

Min

Green

Off

1 of 6 fans Failed on one

Fan Shelf or Tray

Replace fan shelf or tray.

Fan Fail

Red

Maj

Red

Maj

Green

Off

2 Fan Shelves or Trays

Failed

Replace fan shelves or trays.

Input Power

Yellow

Min

A Red

Min

Green

Off

A1-6 Power Fail

Restore DC input power to the A1-6 input terminal.

Input Power

Yellow

Min

B Red

Min

Green

Off

B1-6 Power Fail

Restore DC input power flowing to the B1-6 input

terminal

Input Power

Yellow

Min

A Red

Min

Green

Off

A7-12 Power Fail

Restore DC power to the A7-12 input terminal

Input Power

Yellow

Min

B Red

Min

Green

Off

B7-12 Power Fail

Restore DC power to the B7-12 input terminal.

Input Power

Mul Circuit Fail

Red

Maj

A Red

B Red

Maj

Green

Off

A1-6 & B1-6 Power Fail

Restore DC power to the A1-6 input terminal and

Restore DC power to the B1-6 input terminal

Input Power

Mul Circuit Fail

Red

Maj

A Red

B Red

Maj

Green

Off

A7-12 & B7-12 Power Fail Restore DC power to the A7-12 input terminal.

Restore DC power to the B7-12 input terminal.

Load Drop

Yellow

Min

A, B &

OK

Green

Green

Off

Load Drop

Check the integrity of the circuits going to the load.

Or Adjust load drop threshold to 0 to disable this

feature.

Load Share

Yellow

Min

A, B &

OK

Green

Green

Off

As set of circuits

assigned to one remote

destination are not

sharing current as would

be expected.

Check the integrity of the circuits going to the load.

Or Adjust load share threshold to disable this

feature.

Line Test

A, B &

OK

Green

Green

Off

OK, Fail or Aborted

Estimated line resistance has increased since last

measurement.

Loss Of

Redundancy

Yellow

Min

A, B &

OK

Green

Green

Off

The loss of n additional circuits will cause

customers to lose service.

Check redundancy threshold in the configuration.