Locating failed fans, Figure 25 fan locations – GE Industrial Solutions CPS2400U User Manual

Page 30

Advertising
background image

CPS2400U Upstream System – 19” Product Manual

CPS2400U

850028186 r04 December 2013

30

Table 4 Converter LEDs

Action Required

OK LED

Fault LED

Conditions

Notes

Loss of communication with

controller

Check seating on Alarm card and converter card

Ground fault

Check 5 pin protectors and faults to ground

Overcurrent

or

Under voltage

Check output lines for shorts to each other

Overvoltage

or

Internal failure

Replace Converter Card

Thermal Alarm

Latch alarm after 3 retry

cycles.

Solve thermal problem

Card not powered or input

fuse failure

Check source voltage

Lamp test requested from

controller

Observe Lamp Test

Locating Failed Fans

This information is for reference only. Fan replacement is by Fan Shelf replacement.

The fail LED on the Fan Shelf indicates the position of the failed fan by the number of LED flashes.

Figure 25 Fan Locations

Advertising