Connect Local Network
Step
Action
1.
Connect local network wiring to Fan Shelf connector P6 (RJ-45).
Figure 19 Controller Network Wiring Connection
2.
Check the network connection IP address assigned to the controller.
1. Press the square key,
■
, on the upper right hand corner of the keypad to display the menu.
2. Press the down arrow key,
▼, 2 times to scroll down to the “Status” item on the menu.
3. Press the right arrow,
►, to advance to the “Status” menu.
4. Press the down arrow key,
▼, repeatedly to scroll down to the “Network Settings” item and select by
pressing the right arrow key.
5. Press the right arrow,
►, to advance to the “Network Settings” menu.
6. Press the right arrow,
►, to select Port 1. The P6 connector is Port 1.
7. Read and record the network address for Port 1.
When an IP address is listed connection to the server is confirmed.
P6 10/100 Base-T