1.1.2 FlexLogic Operand States

After each protection pass, all the information regarding each operand's state is updated in
corresponding Modbus register. The section

PLC Interface (Read/Write) on page 110

is the

complete list of registers holding state information of corresponding operand.

1.1.2.1 Breaker Control Flex Operand States

Each breaker has 13 different states shown in

Table 1-2

. Each one of them corresponds to a

different bit in the data item.

Table 1-2 Breaker Control status bit field

The breaker states for all 30 breakers span across 25 consecutive modbus registers as shown in

Table 1-3

. See

PLC Interface (Read/Write) on page 110

for memory locations.

Table 1-3 Breaker status offsets

Bit

Value

Notes

0

Breaker Opened

1

Breaker Closed

2

Breaker Locked Out

3

Closing Spring Charged

4

Primary Disconnect Connected

5

Primary Disconnect Disconnected

6

Secondary Disconnect Connected

7

Breaker Ready

8

Breaker Available

9

Breaker Open Failed

10

Breaker Close Failed

11

Breaker Fault

12

Breaker RELT State

Not used in this release. It shall be always set to 0.

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

N/A

Breaker 2

0

13

This breaker’s information spans
over two adjacent registers

Breaker 3

1

10

This breaker’s information spans
over two adjacent registers

Breaker 4

2

7

This breaker’s information spans
over two adjacent registers

...

...

...

...