1.1.2.3 Ground Fault Flex Operand States
Each breaker has 5 different states shown in
. Each one of them corresponds to a different
bit in the data item.
Table 1-6 Ground Fault status bit field
The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in
. See
PLC Interface (Read/Write) on page 110
for memory locations.
Table 1-7 Ground Fault status offsets
Bit
Value
0
Trip Pickup
1
Trip Operated
2
Trip Dropout
3
Alarm Pickup
4
Alarm Operated
5
Alarm Dropout
Breaker Number
Register
Offset
Bit Offset
Notes
Breaker 1
0
0
Breaker 2
0
6
Breaker 3
0
12
This breaker’s information spans
over two adjacent registers
Breaker 4
1
2
...
...
...
...