Integrator’s Guide

12

1.1.2.3 Ground Fault Flex Operand States

Each breaker has 5 different states shown in

Table 1-6

. Each one of them corresponds to a different

bit in the data item.

Table 1-6 Ground Fault status bit field

The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in

Table 1-7

. See

PLC Interface (Read/Write) on page 110

for memory locations.

Table 1-7 Ground Fault status offsets

Bit

Value

0

Trip Pickup

1

Trip Operated

2

Trip Dropout

3

Alarm Pickup

4

Alarm Operated

5

Alarm Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

6

Breaker 3

0

12

This breaker’s information spans
over two adjacent registers

Breaker 4

1

2

...

...

...

...