GE Industrial Solutions Entellisys 4.0 Integrator's Guide User Manual

Page 42

Advertising
background image

Modbus Memory Map

42

3

0347

Energy Clear Command

0 to 1

---

1

F126

0 (No)

Fault And Event Test Trigger (Read/Write Command)

0348

Fault Trigger Command

0 to 1

---

1

F126

0 (No)

Demand (Read/Write Setting)

0349

Demand Subinterval Length

1 to 60

---

1

F001

1

034A

Demand Subintervals Per Interval

1 to 15

---

1

F001

1

Demand (Read/Write Command)

034B

Demand Reset All Command

0 to 1

---

1

F126

0 (No)

Demand (Read Only)

034C

Number Of Demand Resets All

0 to 4294963200

---

1

F003

0

034E

Last Demand Reset All DateTime

0 to 4294967295

---

1

F050

0

Demand (Read/Write Command)

0350

Demand Log Clear All Command

0 to 1

---

1

F126

0 (No)

Demand (Read Only)

0351

Demand Log Last Cleared All Date

0 to 4294967295

---

1

F050

0

Waveform Capture (Read Only)

035D

Number WF Records Available

0 to 65535

---

1

F001

0

Waveform Capture (Read/Write Command)

035E

Waveform Clear Command

0 to 1

---

1

F126

0 (No)

Waveform Capture (Read Only)

035F

Waveform Last Clear Date

0 to 4294967295

---

1

F050

0

Waveform Capture (Read/Write Command)

0361

Waveform Trigger Command

0 to 1

---

1

F126

0 (No)

Waveform Capture (Read/Write Setting)

0362

Waveform Trigger Mode

0 to 1

---

1

F118

0 (Automatic

Overwrite)

0363

Waveform Trigger Position

0 to 119

Half

Cycles

1

F001

60

Waveform Capture (Read Only)

0364

Waveforms Since Last Clear

0 to 4294967295

---

1

F003

0

0366

Reserved (2 items)

---

---

---

F001

0

Waveform Capture (Read/Write Setting)