Modbus Memory Map

72

3

6C78

Zone X Summation MSGF Alarm Pickup Set-
ting (16 items)

30 to 1200

---

10

F001

1200

6C88

Zone X Summation MSGF Trip or Open

0 to 1

---

1

F727

0 (Open and

don't activate

lockout)

6C89

Zone X Summation Reserved (32 items)

---

---

---

F001

0

6CA9

...Repeated for module number 2

Options (Read Only)

6D4A

Reserved (242 items)

---

---

---

F001

0

6E3C

Options Authentication State

0 to 2

---

1

F738

0 (New and Old

Both Option-

strings Invalid)

6E3D

Options Timestamp

0 to 4294967295

---

1

F050

0

6E3F

Options Bit Vectors

0 to 65535

---

1

F728

0

6E40

Options Expanded Metering Count

0 to 30

---

1

F001

0

Options (Read/Write Setting)

6E41

Option Expanded Metering Node x State
Enable

0 to 4294967295

---

1

F722

0

Options (Read Only)

6E43

Option Demand Metering Count

0 to 30

---

1

F001

0

Options (Read/Write Setting)

6E44

Option Demand Metering Node x State
Enable

0 to 4294967295

---

1

F722

0

Options (Read Only)

6E46

Option Harmonics Metering Count

0 to 30

---

1

F001

0

Options (Read/Write Setting)

6E47

Option Harmonics Metering Node x State
Enable

0 to 4294967295

---

1

F722

0

Options (Read Only)

6E49

Option Voltage Relay Count

0 to 30

---

1

F001

0

Options (Read/Write Setting)

6E4A

Option Voltage Relay Node x State Enable

0 to 4294967295

---

1

F722

0

Options (Read Only)

6E4C

Option High Current Relay Count

0 to 30

---

1

F001

0